7.2 Input Type Selection
Select the input type (in parameter “
tYPE”) from Table below.
TYPE CODE
CHARACTERISTICS
J
0
Range: -50 to 760 °C (-58 to 1400 ºF)
K
1
Range: -90 to 1370 °C (-130 to 2498 ºF)
T
2
Range: -100 to 400 °C (-148 to 752 ºF)
N
3
Range: -90 to 1300 °C (-130 to 2372 ºF)
R
4
Range: 0 to 1760 °C (32 to 3200 ºF)
S
5
Range: 0 to 1760 °C (32 to 3200 ºF)
Pt100
6
Range: -199.9 to 530.0 °C (-328.0 to 986.0 ºF)
Pt100
7
Range: -200 to 530 °C (-328 to 986 ºF)
4-20 mA
8
J Linearization Programmable range: -110 to 760 °C
4-20 mA
9
K Linearization Programmable range: -150 to 1370 °C
4-20 mA
10
T Linearization Programmable range: -160 to 400 °C
4-20 mA
11
N Linearization Programmable range: -90 to 1370°C
4-20 mA
12
R Linearization. Programmable range: 0 to 1760 °C
4-20 mA
13
S Linearization Programmable Range: 0 to 1760 °C
4-20 mA
14
Pt100 Linearization Prog. Range: -200.0 to 530.0 °C
4-20 mA
15
Pt100 Linearization Prog. Range: -200 to 530 °C
0-50 mV
16
Linear. Programmable indication -1999 to 9999
4-20 mA
17
Linear. Programmable indication -1999 to 9999
0 to 5Vdc
18
Linear. Programmable indication -1999 to 9999
4-20 mA
19
Square Root Extraction
7.3 Output and Digital Inputs Configuration
The controller input/output channels can assume multiple functions, depending on
configuration: control output, alarm output, digital output, digital input, and PV or SV analog
retransmission. These channels are identified as I/O1, I/O2, I/O3, I/O4, I/O5 and I/O 6. The basic
controller model comes loaded with:
I/O1 and I/O2 - Relay output SPDT;
I/O3 and I/O4 - Relay output SPST;
I/O5 - Analog output (0-20 or 4-20 mA), pulse, digital I/O;
I/O6 - Digital Input
The function code of each I/O can be selected among the options on Table 2. Only valid
function codes are displayed for each I/O (for example, I/O1, which is a relay, can be configured with